Central Air Conditioning Systems and Design
Central Air Conditioning Systems
Central air conditioning systems condition air or water at a central location and distribute the cooling effect throughout a building. This approach offers superior control, efficiency, and maintenance accessibility compared to distributed systems, making it the preferred solution for commercial buildings, large residential complexes, and institutional facilities.
System Architecture
Central systems separate the generation of cooling from its distribution and delivery. The refrigeration equipment (chillers, cooling towers, boilers) resides in a mechanical room or on the roof, while air handling units (AHUs) or terminal devices serve individual zones.
graph TB
subgraph "Central Plant"
CH[Chiller]
CT[Cooling Tower]
CHWP[Chilled Water Pumps]
CWP[Condenser Water Pumps]
end
subgraph "Distribution System"
CHWL[CHW Supply Line]
CHWR[CHW Return Line]
end
subgraph "Air Side"
AHU1[AHU - Zone 1]
AHU2[AHU - Zone 2]
AHU3[AHU - Zone 3]
FCU[Fan Coil Units]
end
subgraph "Terminal Devices"
VAV[VAV Boxes]
IU[Induction Units]
RB[Radiant Beams]
end
CH -->|Chilled Water| CHWP
CHWP --> CHWL
CHWL --> AHU1
CHWL --> AHU2
CHWL --> AHU3
CHWL --> FCU
AHU1 --> CHWR
AHU2 --> CHWR
AHU3 --> CHWR
FCU --> CHWR
CHWR --> CH
CH -->|Condenser Water| CWP
CWP --> CT
CT -->|Cooled CW| CH
AHU1 --> VAV
AHU2 --> IU
AHU3 --> RB
style CH fill:#e1f5ff
style CT fill:#ffe1e1
style AHU1 fill:#e8f5e9
style AHU2 fill:#e8f5e9
style AHU3 fill:#e8f5e9
System Types
All-Air Systems
All-air systems supply 100% of the sensible and latent cooling capacity through conditioned air. Central AHUs cool, dehumidify, filter, and distribute air through ductwork to occupied spaces.
Characteristics:
- Single-duct constant volume (CV)
- Single-duct variable air volume (VAV)
- Dual-duct systems (hot and cold decks)
- Multizone units
Advantages:
- Precise humidity control through central dehumidification
- Superior air filtration and ventilation control
- No water distribution to occupied spaces (leak risk elimination)
- Flexible zone control with VAV terminals
Design Considerations (ASHRAE 90.1):
- Supply air temperature: 52-58°F for cooling
- Duct velocity: 1,500-2,500 fpm in main ducts
- Maximum static pressure: 3-6 in. w.g. depending on system size
- Outside air economizer required for systems >54,000 Btu/h in most climate zones
Air-Water Systems
Air-water systems use a primary air system to handle ventilation and latent loads, while water-based terminal units (fan coils, induction units, radiant panels) manage sensible cooling.
Characteristics:
- Fan coil units with dedicated outside air system (DOAS)
- Induction units (high-velocity primary air induces room air through coil)
- Radiant cooling panels with ventilation air
Advantages:
- Reduced duct sizes (lower airflow requirements)
- Individual zone control at terminal devices
- Lower fan energy compared to all-air systems
- Quieter operation with properly selected equipment
Design Parameters:
- Primary air quantity: 0.3-0.5 CFM/ft² (ventilation only)
- Chilled water supply: 42-48°F
- Water flow rate: 2-3 GPM per ton of cooling
- Condensate management required at fan coils in humid climates
All-Water Systems
All-water systems eliminate air distribution entirely, using only water to transport cooling capacity. Fan coil units or radiant systems provide space conditioning, with ventilation handled separately or through operable windows (in mild climates).
Characteristics:
- Two-pipe or four-pipe fan coil systems
- Chilled beams (passive or active)
- Radiant ceiling or floor panels
Advantages:
- Minimal space requirements (no ductwork)
- Low energy transport costs (water vs. air: 1 GPM = 500 CFM thermally)
- Easy retrofitting in existing buildings
- Reduced floor-to-floor height requirements
Limitations:
- Limited dehumidification capability
- Potential condensation issues if dew point not controlled
- Separate ventilation system required for IAQ compliance
Water-Source Heat Pumps (WSHP)
Water-source heat pump systems use a common water loop (60-90°F) as a heat source and sink. Individual heat pumps serve zones, rejecting or absorbing heat from the loop.
System Components:
- Distributed heat pumps (0.5-5 tons each)
- Closed-loop water circulation (typically 2-3 GPM per ton)
- Boiler for loop heating (winter)
- Cooling tower or fluid cooler for heat rejection (summer)
Advantages:
- Simultaneous heating and cooling capability
- Heat recovery between zones (perimeter heating uses core cooling)
- No refrigerant piping throughout building
- Individual zone control and metering
Design Guidelines (ASHRAE Handbook - HVAC Systems and Equipment):
- Loop temperature range: 60-90°F (optimal: 70-80°F)
- Pipe sizing: 2-4 fps water velocity
- Buffer tank: 1.5-3 gallons per ton of connected load
- Tower capacity: 60-80% of total heat pump capacity
Central Plant Design Considerations
Chiller Selection
| Parameter | Water-Cooled | Air-Cooled | Evaporative-Cooled |
|---|---|---|---|
| Efficiency (kW/ton) | 0.45-0.65 | 0.85-1.20 | 0.55-0.75 |
| Footprint | Smaller | Larger | Medium |
| Water Consumption | High | None | Medium |
| Maintenance | Moderate | Low | Moderate |
| First Cost | Higher | Lower | Medium |
| Noise Level | Low | High | Medium |
Chilled Water System Design
Temperature Differential:
- Standard: 44°F supply / 54°F return (10°F ΔT)
- High ΔT: 40°F supply / 56°F return (16°F ΔT)
- Low-temperature: 38°F supply for high sensible load applications
Pumping Strategies:
- Primary-only: Single pump loop, constant or variable flow
- Primary-secondary: Decoupled production and distribution
- Variable primary flow: Eliminates secondary pumps, requires careful control
Pipe Sizing:
- Velocity: 4-8 fps in mains, 2-4 fps in branches
- Pressure drop: 2-4 ft per 100 ft of pipe
- Flow rate: Q (GPM) = Cooling Load (Btu/h) / (500 × ΔT°F)
Load Diversity and Sizing
Central systems benefit from load diversity. Peak loads do not occur simultaneously across all zones.
Diversity Factors (ASHRAE Fundamentals):
- Office buildings: 0.75-0.85
- Hotels: 0.70-0.80
- Hospitals: 0.85-0.95
- Retail: 0.90-1.00
Total system capacity = Sum of zone loads × Diversity factor
Energy Efficiency Strategies
Variable Flow Systems:
- Two-way control valves at coils enable variable primary flow
- VFD-controlled pumps reduce energy at part load
- Minimum flow bypass maintains chiller evaporator flow
Free Cooling:
- Waterside economizer using cooling tower when outdoor wet-bulb permits
- Airside economizer for all-air systems in appropriate climates
- ASHRAE 90.1 requires economizers for systems >54,000 Btu/h
Chiller Sequencing:
- Stage multiple chillers based on load
- Operate chillers at optimal efficiency points
- Consider thermal storage for demand management
Comparison of Central System Approaches
| System Type | Distribution | Terminal Device | Humidity Control | Space Requirements | Typical Application |
|---|---|---|---|---|---|
| All-Air VAV | Ductwork | VAV boxes | Excellent | High (ducts) | Office buildings, laboratories |
| Air-Water | Ducts + Pipes | Fan coils | Good | Moderate | Hotels, apartments, offices |
| All-Water | Pipes only | Fan coils, beams | Limited | Low | Retrofits, high-rise residential |
| WSHP | Water loop | Heat pumps | Moderate | Low-Moderate | Schools, offices, mixed-use |
Design Process and Guidelines
ASHRAE Standard 62.1 Compliance:
- Minimum ventilation rates based on occupancy and space type
- Ventilation effectiveness factors for air distribution
- Demand-controlled ventilation for variable occupancy spaces
Load Calculation (ASHRAE Fundamentals):
- Calculate block loads for central equipment sizing
- Calculate zone loads for distribution system and terminal device sizing
- Apply diversity factors appropriate to building type
- Include safety factors judiciously (10-15% maximum)
Sequence of Design:
- Establish space conditions and loads
- Select system type based on building requirements
- Size central plant equipment with diversity
- Design distribution system (ductwork or piping)
- Select and locate terminal devices
- Develop control sequences
- Verify energy code compliance
Central air conditioning systems represent the most flexible and scalable approach to building climate control. Proper design requires understanding the physical principles of heat transfer, fluid mechanics, and psychrometrics, combined with application of ASHRAE standards and manufacturer data. The selection between all-air, air-water, all-water, or water-source approaches depends on building type, climate, spatial constraints, and operational requirements.
Sections
All-Air HVAC Systems: Design & Configuration
Comprehensive guide to all-air HVAC systems including CAV, VAV, dual duct, and multizone configurations. Covers airflow fundamentals, duct sizing per ASHRAE standards.
All-Water HVAC Systems: Design & Configuration Guide
Comprehensive guide to all-water HVAC systems including fan coil units, radiant panels, chilled beams, and 2-pipe vs 4-pipe system configurations with performance comparisons.
Air-Water Systems: Induction & Fan Coil Units
Comprehensive guide to air-water HVAC systems including primary air configurations, induction units, fan coil systems, and ASHRAE selection criteria for optimal performance.