HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Central Air Conditioning Systems and Design

Central Air Conditioning Systems

Central air conditioning systems condition air or water at a central location and distribute the cooling effect throughout a building. This approach offers superior control, efficiency, and maintenance accessibility compared to distributed systems, making it the preferred solution for commercial buildings, large residential complexes, and institutional facilities.

System Architecture

Central systems separate the generation of cooling from its distribution and delivery. The refrigeration equipment (chillers, cooling towers, boilers) resides in a mechanical room or on the roof, while air handling units (AHUs) or terminal devices serve individual zones.

graph TB
    subgraph "Central Plant"
        CH[Chiller]
        CT[Cooling Tower]
        CHWP[Chilled Water Pumps]
        CWP[Condenser Water Pumps]
    end

    subgraph "Distribution System"
        CHWL[CHW Supply Line]
        CHWR[CHW Return Line]
    end

    subgraph "Air Side"
        AHU1[AHU - Zone 1]
        AHU2[AHU - Zone 2]
        AHU3[AHU - Zone 3]
        FCU[Fan Coil Units]
    end

    subgraph "Terminal Devices"
        VAV[VAV Boxes]
        IU[Induction Units]
        RB[Radiant Beams]
    end

    CH -->|Chilled Water| CHWP
    CHWP --> CHWL
    CHWL --> AHU1
    CHWL --> AHU2
    CHWL --> AHU3
    CHWL --> FCU
    AHU1 --> CHWR
    AHU2 --> CHWR
    AHU3 --> CHWR
    FCU --> CHWR
    CHWR --> CH

    CH -->|Condenser Water| CWP
    CWP --> CT
    CT -->|Cooled CW| CH

    AHU1 --> VAV
    AHU2 --> IU
    AHU3 --> RB

    style CH fill:#e1f5ff
    style CT fill:#ffe1e1
    style AHU1 fill:#e8f5e9
    style AHU2 fill:#e8f5e9
    style AHU3 fill:#e8f5e9

System Types

All-Air Systems

All-air systems supply 100% of the sensible and latent cooling capacity through conditioned air. Central AHUs cool, dehumidify, filter, and distribute air through ductwork to occupied spaces.

Characteristics:

  • Single-duct constant volume (CV)
  • Single-duct variable air volume (VAV)
  • Dual-duct systems (hot and cold decks)
  • Multizone units

Advantages:

  • Precise humidity control through central dehumidification
  • Superior air filtration and ventilation control
  • No water distribution to occupied spaces (leak risk elimination)
  • Flexible zone control with VAV terminals

Design Considerations (ASHRAE 90.1):

  • Supply air temperature: 52-58°F for cooling
  • Duct velocity: 1,500-2,500 fpm in main ducts
  • Maximum static pressure: 3-6 in. w.g. depending on system size
  • Outside air economizer required for systems >54,000 Btu/h in most climate zones

Air-Water Systems

Air-water systems use a primary air system to handle ventilation and latent loads, while water-based terminal units (fan coils, induction units, radiant panels) manage sensible cooling.

Characteristics:

  • Fan coil units with dedicated outside air system (DOAS)
  • Induction units (high-velocity primary air induces room air through coil)
  • Radiant cooling panels with ventilation air

Advantages:

  • Reduced duct sizes (lower airflow requirements)
  • Individual zone control at terminal devices
  • Lower fan energy compared to all-air systems
  • Quieter operation with properly selected equipment

Design Parameters:

  • Primary air quantity: 0.3-0.5 CFM/ft² (ventilation only)
  • Chilled water supply: 42-48°F
  • Water flow rate: 2-3 GPM per ton of cooling
  • Condensate management required at fan coils in humid climates

All-Water Systems

All-water systems eliminate air distribution entirely, using only water to transport cooling capacity. Fan coil units or radiant systems provide space conditioning, with ventilation handled separately or through operable windows (in mild climates).

Characteristics:

  • Two-pipe or four-pipe fan coil systems
  • Chilled beams (passive or active)
  • Radiant ceiling or floor panels

Advantages:

  • Minimal space requirements (no ductwork)
  • Low energy transport costs (water vs. air: 1 GPM = 500 CFM thermally)
  • Easy retrofitting in existing buildings
  • Reduced floor-to-floor height requirements

Limitations:

  • Limited dehumidification capability
  • Potential condensation issues if dew point not controlled
  • Separate ventilation system required for IAQ compliance

Water-Source Heat Pumps (WSHP)

Water-source heat pump systems use a common water loop (60-90°F) as a heat source and sink. Individual heat pumps serve zones, rejecting or absorbing heat from the loop.

System Components:

  • Distributed heat pumps (0.5-5 tons each)
  • Closed-loop water circulation (typically 2-3 GPM per ton)
  • Boiler for loop heating (winter)
  • Cooling tower or fluid cooler for heat rejection (summer)

Advantages:

  • Simultaneous heating and cooling capability
  • Heat recovery between zones (perimeter heating uses core cooling)
  • No refrigerant piping throughout building
  • Individual zone control and metering

Design Guidelines (ASHRAE Handbook - HVAC Systems and Equipment):

  • Loop temperature range: 60-90°F (optimal: 70-80°F)
  • Pipe sizing: 2-4 fps water velocity
  • Buffer tank: 1.5-3 gallons per ton of connected load
  • Tower capacity: 60-80% of total heat pump capacity

Central Plant Design Considerations

Chiller Selection

ParameterWater-CooledAir-CooledEvaporative-Cooled
Efficiency (kW/ton)0.45-0.650.85-1.200.55-0.75
FootprintSmallerLargerMedium
Water ConsumptionHighNoneMedium
MaintenanceModerateLowModerate
First CostHigherLowerMedium
Noise LevelLowHighMedium

Chilled Water System Design

Temperature Differential:

  • Standard: 44°F supply / 54°F return (10°F ΔT)
  • High ΔT: 40°F supply / 56°F return (16°F ΔT)
  • Low-temperature: 38°F supply for high sensible load applications

Pumping Strategies:

  • Primary-only: Single pump loop, constant or variable flow
  • Primary-secondary: Decoupled production and distribution
  • Variable primary flow: Eliminates secondary pumps, requires careful control

Pipe Sizing:

  • Velocity: 4-8 fps in mains, 2-4 fps in branches
  • Pressure drop: 2-4 ft per 100 ft of pipe
  • Flow rate: Q (GPM) = Cooling Load (Btu/h) / (500 × ΔT°F)

Load Diversity and Sizing

Central systems benefit from load diversity. Peak loads do not occur simultaneously across all zones.

Diversity Factors (ASHRAE Fundamentals):

  • Office buildings: 0.75-0.85
  • Hotels: 0.70-0.80
  • Hospitals: 0.85-0.95
  • Retail: 0.90-1.00

Total system capacity = Sum of zone loads × Diversity factor

Energy Efficiency Strategies

Variable Flow Systems:

  • Two-way control valves at coils enable variable primary flow
  • VFD-controlled pumps reduce energy at part load
  • Minimum flow bypass maintains chiller evaporator flow

Free Cooling:

  • Waterside economizer using cooling tower when outdoor wet-bulb permits
  • Airside economizer for all-air systems in appropriate climates
  • ASHRAE 90.1 requires economizers for systems >54,000 Btu/h

Chiller Sequencing:

  • Stage multiple chillers based on load
  • Operate chillers at optimal efficiency points
  • Consider thermal storage for demand management

Comparison of Central System Approaches

System TypeDistributionTerminal DeviceHumidity ControlSpace RequirementsTypical Application
All-Air VAVDuctworkVAV boxesExcellentHigh (ducts)Office buildings, laboratories
Air-WaterDucts + PipesFan coilsGoodModerateHotels, apartments, offices
All-WaterPipes onlyFan coils, beamsLimitedLowRetrofits, high-rise residential
WSHPWater loopHeat pumpsModerateLow-ModerateSchools, offices, mixed-use

Design Process and Guidelines

ASHRAE Standard 62.1 Compliance:

  • Minimum ventilation rates based on occupancy and space type
  • Ventilation effectiveness factors for air distribution
  • Demand-controlled ventilation for variable occupancy spaces

Load Calculation (ASHRAE Fundamentals):

  1. Calculate block loads for central equipment sizing
  2. Calculate zone loads for distribution system and terminal device sizing
  3. Apply diversity factors appropriate to building type
  4. Include safety factors judiciously (10-15% maximum)

Sequence of Design:

  1. Establish space conditions and loads
  2. Select system type based on building requirements
  3. Size central plant equipment with diversity
  4. Design distribution system (ductwork or piping)
  5. Select and locate terminal devices
  6. Develop control sequences
  7. Verify energy code compliance

Central air conditioning systems represent the most flexible and scalable approach to building climate control. Proper design requires understanding the physical principles of heat transfer, fluid mechanics, and psychrometrics, combined with application of ASHRAE standards and manufacturer data. The selection between all-air, air-water, all-water, or water-source approaches depends on building type, climate, spatial constraints, and operational requirements.

Sections

All-Air HVAC Systems: Design & Configuration

Comprehensive guide to all-air HVAC systems including CAV, VAV, dual duct, and multizone configurations. Covers airflow fundamentals, duct sizing per ASHRAE standards.

All-Water HVAC Systems: Design & Configuration Guide

Comprehensive guide to all-water HVAC systems including fan coil units, radiant panels, chilled beams, and 2-pipe vs 4-pipe system configurations with performance comparisons.

Air-Water Systems: Induction & Fan Coil Units

Comprehensive guide to air-water HVAC systems including primary air configurations, induction units, fan coil systems, and ASHRAE selection criteria for optimal performance.