Two-Stage Evaporative Cooling
Two-stage evaporative cooling combines indirect and direct stages to achieve supply air temperatures below the outdoor wet-bulb temperature—a thermodynamic impossibility with single-stage systems. This configuration maximizes evaporative cooling effectiveness while managing humidity addition.
System Configuration
Indirect-Direct Arrangement
The standard two-stage configuration:
Stage 1 - Indirect Evaporative Cooling (IEC):
- Pre-cools outdoor air sensibly
- No moisture addition to supply air
- Reduces dry-bulb without affecting wet-bulb
- Sets up favorable conditions for Stage 2
Stage 2 - Direct Evaporative Cooling (DEC):
- Further cools pre-cooled air
- Adds moisture through adiabatic saturation
- Achieves lowest possible supply temperature
Process Path on Psychrometric Chart
Outdoor Air → [IEC: horizontal left] → [DEC: diagonal toward saturation] → Supply
The two-stage process reaches lower temperatures because Stage 1 reduces the dry-bulb while the wet-bulb remains unchanged, increasing the wet-bulb depression available for Stage 2.
Thermodynamic Analysis
Stage 1: Indirect Cooling
$$T_{1,out} = T_{OA} - \epsilon_{IEC}(T_{OA} - T_{wb,OA})$$
The wet-bulb temperature remains constant: $$T_{wb,1} = T_{wb,OA}$$
Stage 2: Direct Cooling
Using pre-cooled air with unchanged wet-bulb: $$T_{supply} = T_{1,out} - \epsilon_{DEC}(T_{1,out} - T_{wb,1})$$
Combined Effectiveness
Overall wet-bulb effectiveness exceeds either stage alone:
$$\epsilon_{total} = \epsilon_{IEC} + \epsilon_{DEC}(1 - \epsilon_{IEC})$$
Example: εIEC = 70%, εDEC = 85% $$\epsilon_{total} = 0.70 + 0.85(1 - 0.70) = 0.70 + 0.255 = 0.955$$
Sub-Wet-Bulb Achievement
Two-stage systems achieve supply temperatures below outdoor wet-bulb when: $$T_{supply} < T_{wb,OA}$$
This occurs when combined effectiveness exceeds 100%: $$T_{supply} = T_{OA} - \epsilon_{total}(T_{OA} - T_{wb,OA})$$
Performance Example
Design Conditions: 105°F DB / 70°F WB outdoor
Stage 1 (IEC, 70% effective):
- Temperature drop: 0.70 × (105 - 70) = 24.5°F
- After Stage 1: 105 - 24.5 = 80.5°F DB / 70°F WB
Stage 2 (DEC, 85% effective):
- Temperature drop: 0.85 × (80.5 - 70) = 8.9°F
- Supply air: 80.5 - 8.9 = 71.6°F DB
Result: Supply air (71.6°F) is below outdoor wet-bulb (70°F)!
Performance Comparison
| Condition | DEC Only | Two-Stage |
|---|---|---|
| 105°F/70°F WB | 75°F | 71.6°F |
| 100°F/66°F WB | 71°F | 68.3°F |
| 95°F/65°F WB | 70°F | 67.6°F |
System Components
Integrated Packaged Units
Factory-assembled two-stage coolers:
Components:
- Indirect heat exchanger (plate or tube)
- Direct media section (rigid cellulose)
- Two water systems (may share sump)
- Separate or common fans
- Integrated controls
Capacities: 3,000-30,000+ CFM
Built-Up Systems
Custom configurations for large installations:
- Separate IEC and DEC modules
- Central station AHU integration
- Multiple stages for ultra-low temperatures
- Process cooling applications
Water Systems
Each stage requires water management:
IEC Water System:
- Secondary airstream wetting
- Recirculating pump
- Lower evaporation rate
- Bleed-off for concentration control
DEC Water System:
- Media wetting distribution
- Higher evaporation rate
- Combined or separate sump options
Control Strategies
Staged Operation
Sequential control based on conditions:
- Mild conditions: IEC only
- Warm conditions: IEC + DEC
- Hot conditions: Maximum staging
Variable Speed Control
Modulating fan speeds optimize efficiency:
- Primary fan: Matches supply CFM demand
- Secondary fan: Balances effectiveness vs. energy
- Pumps: Ensure adequate wetting
Leaving Air Temperature Control
Supply temperature setpoint control:
$$T_{setpoint} = f(outdoor\ conditions,\ load)$$
Controller modulates stages to maintain setpoint.
Energy Performance
Comparison with Mechanical Cooling
Two-stage evaporative vs. DX cooling:
| Metric | Two-Stage Evap | DX Cooling |
|---|---|---|
| EER | 30-50 | 10-14 |
| Peak kW/ton | 0.3-0.5 | 0.9-1.2 |
| Water use | 3-4 gal/ton·hr | 0 |
| Peak demand | 60-75% reduction | Baseline |
Annual Energy Analysis
Bin analysis determines annual performance:
$$Energy_{annual} = \sum_{bins} hours_i \times \frac{Q_i}{EER_i}$$
Compare two-stage evaporative, single-stage, and mechanical systems for lifecycle cost.
Applications
Commercial Buildings
Excellent fit for:
- Office buildings in dry climates
- Retail and big-box stores
- Schools and universities
- Gymnasiums and recreation
Industrial Facilities
Process and comfort cooling:
- Manufacturing plants
- Warehouses
- Aircraft hangars
- Assembly facilities
Data Centers
Growing application:
- Free cooling hours maximized
- PUE improvement
- Backup mechanical for peak
- ASHRAE climate zones 1-5
Design Considerations
Climate Suitability
Two-stage most effective when:
- Outdoor RH < 50% design
- Wet-bulb depression > 20°F
- Hot-dry summer climate
- Extended cooling season
Humidity Management
Stage 2 adds moisture—consider:
- Leaving humidity acceptable for application
- Ventilation rate dilutes indoor humidity
- Bypass damper for humidity-sensitive periods
First Cost vs. Operating Cost
Higher equipment cost offset by:
- Lower operating energy
- Reduced peak demand charges
- Lower maintenance than mechanical
Water Availability
Total consumption both stages: $$\dot{m}{water} ≈ \frac{Q{total}}{h_{fg}} + Bleed$$
Typically 4-6 gal/ton·hr total
Two-stage evaporative cooling provides the ultimate evaporative cooling performance, achieving supply temperatures impossible with single-stage systems while maintaining exceptional energy efficiency in appropriate climates.