HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Two-Stage Evaporative Cooling

Two-stage evaporative cooling combines indirect and direct stages to achieve supply air temperatures below the outdoor wet-bulb temperature—a thermodynamic impossibility with single-stage systems. This configuration maximizes evaporative cooling effectiveness while managing humidity addition.

System Configuration

Indirect-Direct Arrangement

The standard two-stage configuration:

Stage 1 - Indirect Evaporative Cooling (IEC):

  • Pre-cools outdoor air sensibly
  • No moisture addition to supply air
  • Reduces dry-bulb without affecting wet-bulb
  • Sets up favorable conditions for Stage 2

Stage 2 - Direct Evaporative Cooling (DEC):

  • Further cools pre-cooled air
  • Adds moisture through adiabatic saturation
  • Achieves lowest possible supply temperature

Process Path on Psychrometric Chart

Outdoor Air → [IEC: horizontal left] → [DEC: diagonal toward saturation] → Supply

The two-stage process reaches lower temperatures because Stage 1 reduces the dry-bulb while the wet-bulb remains unchanged, increasing the wet-bulb depression available for Stage 2.

Thermodynamic Analysis

Stage 1: Indirect Cooling

$$T_{1,out} = T_{OA} - \epsilon_{IEC}(T_{OA} - T_{wb,OA})$$

The wet-bulb temperature remains constant: $$T_{wb,1} = T_{wb,OA}$$

Stage 2: Direct Cooling

Using pre-cooled air with unchanged wet-bulb: $$T_{supply} = T_{1,out} - \epsilon_{DEC}(T_{1,out} - T_{wb,1})$$

Combined Effectiveness

Overall wet-bulb effectiveness exceeds either stage alone:

$$\epsilon_{total} = \epsilon_{IEC} + \epsilon_{DEC}(1 - \epsilon_{IEC})$$

Example: εIEC = 70%, εDEC = 85% $$\epsilon_{total} = 0.70 + 0.85(1 - 0.70) = 0.70 + 0.255 = 0.955$$

Sub-Wet-Bulb Achievement

Two-stage systems achieve supply temperatures below outdoor wet-bulb when: $$T_{supply} < T_{wb,OA}$$

This occurs when combined effectiveness exceeds 100%: $$T_{supply} = T_{OA} - \epsilon_{total}(T_{OA} - T_{wb,OA})$$

Performance Example

Design Conditions: 105°F DB / 70°F WB outdoor

Stage 1 (IEC, 70% effective):

  • Temperature drop: 0.70 × (105 - 70) = 24.5°F
  • After Stage 1: 105 - 24.5 = 80.5°F DB / 70°F WB

Stage 2 (DEC, 85% effective):

  • Temperature drop: 0.85 × (80.5 - 70) = 8.9°F
  • Supply air: 80.5 - 8.9 = 71.6°F DB

Result: Supply air (71.6°F) is below outdoor wet-bulb (70°F)!

Performance Comparison

ConditionDEC OnlyTwo-Stage
105°F/70°F WB75°F71.6°F
100°F/66°F WB71°F68.3°F
95°F/65°F WB70°F67.6°F

System Components

Integrated Packaged Units

Factory-assembled two-stage coolers:

Components:

  • Indirect heat exchanger (plate or tube)
  • Direct media section (rigid cellulose)
  • Two water systems (may share sump)
  • Separate or common fans
  • Integrated controls

Capacities: 3,000-30,000+ CFM

Built-Up Systems

Custom configurations for large installations:

  • Separate IEC and DEC modules
  • Central station AHU integration
  • Multiple stages for ultra-low temperatures
  • Process cooling applications

Water Systems

Each stage requires water management:

IEC Water System:

  • Secondary airstream wetting
  • Recirculating pump
  • Lower evaporation rate
  • Bleed-off for concentration control

DEC Water System:

  • Media wetting distribution
  • Higher evaporation rate
  • Combined or separate sump options

Control Strategies

Staged Operation

Sequential control based on conditions:

  1. Mild conditions: IEC only
  2. Warm conditions: IEC + DEC
  3. Hot conditions: Maximum staging

Variable Speed Control

Modulating fan speeds optimize efficiency:

  • Primary fan: Matches supply CFM demand
  • Secondary fan: Balances effectiveness vs. energy
  • Pumps: Ensure adequate wetting

Leaving Air Temperature Control

Supply temperature setpoint control:

$$T_{setpoint} = f(outdoor\ conditions,\ load)$$

Controller modulates stages to maintain setpoint.

Energy Performance

Comparison with Mechanical Cooling

Two-stage evaporative vs. DX cooling:

MetricTwo-Stage EvapDX Cooling
EER30-5010-14
Peak kW/ton0.3-0.50.9-1.2
Water use3-4 gal/ton·hr0
Peak demand60-75% reductionBaseline

Annual Energy Analysis

Bin analysis determines annual performance:

$$Energy_{annual} = \sum_{bins} hours_i \times \frac{Q_i}{EER_i}$$

Compare two-stage evaporative, single-stage, and mechanical systems for lifecycle cost.

Applications

Commercial Buildings

Excellent fit for:

  • Office buildings in dry climates
  • Retail and big-box stores
  • Schools and universities
  • Gymnasiums and recreation

Industrial Facilities

Process and comfort cooling:

  • Manufacturing plants
  • Warehouses
  • Aircraft hangars
  • Assembly facilities

Data Centers

Growing application:

  • Free cooling hours maximized
  • PUE improvement
  • Backup mechanical for peak
  • ASHRAE climate zones 1-5

Design Considerations

Climate Suitability

Two-stage most effective when:

  • Outdoor RH < 50% design
  • Wet-bulb depression > 20°F
  • Hot-dry summer climate
  • Extended cooling season

Humidity Management

Stage 2 adds moisture—consider:

  • Leaving humidity acceptable for application
  • Ventilation rate dilutes indoor humidity
  • Bypass damper for humidity-sensitive periods

First Cost vs. Operating Cost

Higher equipment cost offset by:

  • Lower operating energy
  • Reduced peak demand charges
  • Lower maintenance than mechanical

Water Availability

Total consumption both stages: $$\dot{m}{water} ≈ \frac{Q{total}}{h_{fg}} + Bleed$$

Typically 4-6 gal/ton·hr total

Two-stage evaporative cooling provides the ultimate evaporative cooling performance, achieving supply temperatures impossible with single-stage systems while maintaining exceptional energy efficiency in appropriate climates.