Evaporative Cooler Selection
Proper evaporative cooler selection ensures systems deliver required cooling capacity efficiently across expected operating conditions. This guide covers system sizing, equipment type selection, and performance verification for successful installations.
Climate Analysis
Wet-Bulb Frequency Analysis
Before selecting evaporative cooling, analyze local climate data:
Bin Data Analysis:
- Compile hourly wet-bulb temperatures
- Determine hours in each temperature bin
- Calculate cooling degree-hours
- Identify percentage hours evaporative cooling viable
Selection Criteria:
| Climate Category | Design WB | Hours > 65°F WB | Suitability |
|---|---|---|---|
| Excellent | <62°F | <100 | Direct or Two-Stage |
| Good | 62-67°F | 100-300 | Two-Stage or Hybrid |
| Marginal | 67-72°F | 300-600 | Indirect or Hybrid |
| Poor | >72°F | >600 | Pre-cooling only |
Design Point Selection
Select design conditions for sizing:
Conservative Approach: 1% annual wet-bulb Standard Approach: 2.5% annual wet-bulb Economy Approach: 5% annual wet-bulb
More conservative selection provides more hours of comfort but increases equipment size.
Capacity Calculation
Sensible Cooling Load
Determine space sensible cooling requirement:
$$Q_{sensible} = Q_{transmission} + Q_{solar} + Q_{internal} + Q_{infiltration}$$
Note: Evaporative cooling primarily addresses sensible loads; latent removal is limited.
Airflow Calculation
Required airflow for sensible cooling:
$$CFM = \frac{Q_{sensible}}{1.08 \times (T_{room} - T_{supply})}$$
Where:
- $T_{room}$ = design indoor temperature
- $T_{supply}$ = achievable supply temperature
Supply Temperature Estimation
Estimate achievable supply temperature:
Direct Evaporative: $$T_{supply} = T_{db,OA} - \epsilon_{DEC}(T_{db,OA} - T_{wb,OA})$$
Two-Stage: $$T_{supply} = T_{db,OA} - [\epsilon_{IEC} + \epsilon_{DEC}(1-\epsilon_{IEC})](T_{db,OA} - T_{wb,OA})$$
Equipment Type Selection
Direct Evaporative Coolers
Select When:
- Design wet-bulb <65°F
- Humidity addition acceptable
- Lowest first cost required
- Simple installation preferred
Typical Effectiveness: 70-90%
Indirect Evaporative Coolers
Select When:
- Supply humidity must be controlled
- Moderate humidity climates
- Humidity-sensitive applications
- Higher first cost acceptable
Typical Effectiveness: 50-75% (wet-bulb)
Two-Stage Systems
Select When:
- Maximum cooling required
- Moderate humidity acceptable
- Climate supports both stages
- Energy savings justify cost
Typical Effectiveness: 90-115% (wet-bulb)
Hybrid Systems
Select When:
- Evaporative cooling marginal
- Backup cooling required
- Variable climate conditions
- Peak load beyond evaporative capacity
Equipment Sizing
Face Area Sizing
Media face area determines capacity:
$$A_{face} = \frac{CFM}{V_{face}}$$
Recommended Face Velocities:
| Media Type | Velocity Range | Optimal |
|---|---|---|
| Rigid cellulose | 400-600 fpm | 500 fpm |
| Aspen pad | 250-400 fpm | 300 fpm |
| IEC plate | 400-600 fpm | 500 fpm |
Media Depth Selection
Deeper media increases effectiveness and pressure drop:
| Depth | Effectiveness | ΔP | Application |
|---|---|---|---|
| 6" | 70-75% | 0.1" | Residential, economy |
| 8" | 80-85% | 0.15" | Light commercial |
| 12" | 85-90% | 0.25" | Commercial standard |
| 18" | 90-95% | 0.35" | High performance |
Fan Sizing
Fan must overcome total static pressure:
$$\Delta P_{total} = \Delta P_{media} + \Delta P_{intake} + \Delta P_{duct} + \Delta P_{outlet}$$
Select fan for design CFM at total static, with margin for loaded media.
Water System Sizing
Evaporation Rate
Water consumption for cooling:
$$\dot{m}{evap} = \frac{Q{sensible}}{h_{fg}} ≈ 3\ gal/ton \cdot hr$$
Bleed-Off Requirements
Prevent mineral concentration:
$$Bleed\ Rate = \frac{Evap\ Rate}{Cycles - 1}$$
Where cycles of concentration = 3-5 typical
Total Water: 4-5 gal/ton·hr including bleed
Sump Sizing
Sump capacity for adequate reserve:
- Minimum: 5-10 gallons per ft² face area
- Or: 3-5 minutes pump flow capacity
Performance Verification
Commissioning Tests
Verify installed performance:
- Airflow measurement: Compare to design CFM
- Temperature drop: Verify effectiveness
- Pressure drop: Check fan operating point
- Water distribution: Confirm media wetting
Effectiveness Verification
Calculate actual effectiveness:
$$\epsilon_{actual} = \frac{T_{in} - T_{out}}{T_{in} - T_{wb,in}}$$
Compare to published performance curves.
Energy Performance
Measure EER or kW/ton:
$$EER = \frac{Q_{cooling}}{W_{total}}$$
Compare to design values and alternatives.
Selection Documentation
Equipment Schedule
Document selections:
| Item | Value |
|---|---|
| Model/Manufacturer | |
| Airflow (CFM) | |
| Effectiveness (%) | |
| Supply air temp (design) | |
| Fan HP | |
| Pump GPM | |
| Water consumption | |
| Electrical (V/Ph/Hz) |
Operating Limits
Specify operating parameters:
- Maximum wet-bulb for evaporative mode
- Changeover points for hybrid systems
- Maintenance schedules
- Media replacement criteria
Careful evaporative cooler selection, matched to climate conditions and application requirements, ensures systems deliver expected performance while maximizing energy savings.