Chilled Water Systems for Cooling Applications
Chilled water systems represent the primary cooling distribution method for medium to large commercial, institutional, and industrial facilities. Unlike direct expansion refrigeration systems that distribute refrigerant, chilled water systems use water as a secondary heat transfer medium, providing superior flexibility in zoning, capacity modulation, and central plant optimization. This analysis examines the fundamental physics, system configurations, component selection methodologies, and energy optimization strategies governing chilled water system design.
Fundamental System Physics
Heat Transfer Fundamentals
The cooling capacity delivered by a chilled water system derives from sensible heat transfer between the chilled water and the conditioned space air. The fundamental energy balance equation governs system sizing:
Where:
- $\dot{Q}$ = cooling capacity (kW or tons)
- $\dot{m}$ = mass flow rate (kg/s or lb/hr)
- $c_p$ = specific heat of water = 4.186 kJ/(kg·K) or 1.0 Btu/(lb·°F)
- $\Delta T$ = supply-return temperature difference (°C or °F)
- $\rho$ = water density = 1000 kg/m³ or 8.33 lb/gal
- $\dot{V}$ = volumetric flow rate (m³/s, L/s, or gpm)
For water systems using standard units:
Design Delta-T Selection
The temperature difference between supply and return water fundamentally impacts system economics. Larger delta-T values reduce flow rate requirements, enabling smaller pipes, pumps, and reduced pumping energy, but may compromise heat transfer effectiveness at terminal units.
Standard design delta-T values:
- 10°F (5.6°C): Traditional design, conservative approach
- 12-14°F (6.7-7.8°C): Modern practice balancing equipment performance and pumping energy
- 16-20°F (8.9-11.1°C): High delta-T systems requiring careful terminal unit selection
Flow rate calculation for a given delta-T:
Example: 500-ton cooling load with 12°F delta-T requires:
Delta-T Syndrome
Delta-T degradation represents a persistent operational challenge where actual system delta-T falls below design values, causing excessive flow rates and pump energy consumption. Primary causes include:
- Coil bypass flow: Improperly balanced terminal units allowing water to bypass coils
- Oversized pumps: Excessive flow overcoming control valve authority
- Low load conditions: Reduced heat transfer at partial load with constant flow
- Chiller control: Supply temperature reset reducing delta-T
- Piping design: Short-circuiting or unbalanced distribution
The energy impact scales significantly:
A 20% increase in flow rate from delta-T degradation (12°F design to 10°F actual) increases pump energy by:
System Configurations
Primary-Secondary (Decoupled) Systems
Primary-secondary pumping decouples chiller flow (primary loop) from distribution flow (secondary loop) using a common pipe or decoupler. This configuration allows chillers to operate at optimal flow rates independent of building load variations.
graph TD
CH1[Chiller 1] -->|Primary Pump 1| CP[Common Pipe]
CH2[Chiller 2] -->|Primary Pump 2| CP
CH3[Chiller 3] -->|Primary Pump 3| CP
CP -->|Secondary Pump 1| LOAD1[Building Load 1]
CP -->|Secondary Pump 2| LOAD2[Building Load 2]
CP -->|Secondary Pump 3| LOAD3[Building Load 3]
LOAD1 --> CP
LOAD2 --> CP
LOAD3 --> CP
Common Pipe Sizing
The common pipe must maintain low pressure drop to prevent primary-secondary interaction. Velocity should not exceed 2-4 ft/s (0.6-1.2 m/s):
Where:
- $v$ = velocity (ft/s)
- $\dot{V}$ = flow rate (ft³/s, converted from gpm: gpm/448.8)
- $D$ = pipe diameter (ft)
Common pipe length should be minimized (typically 10-20 pipe diameters) to reduce mixing and maintain temperature separation.
Flow Relationships
Three operating conditions exist:
- Primary flow > Secondary flow: Excess chilled water returns through common pipe to chillers (rare)
- Primary flow = Secondary flow: Ideal balanced condition
- Primary flow < Secondary flow: Return water bypasses through common pipe, mixing with supply (typical at partial load)
The mixing temperature when secondary exceeds primary:
Variable Primary Flow (VPF)
Variable primary flow eliminates the secondary loop, using variable speed drives on primary pumps to modulate flow based on building demand. This configuration reduces pump count, initial cost, and pumping energy but requires careful chiller minimum flow protection.
graph TD
VFD1[VFD Primary Pump 1] --> CH1[Chiller 1]
VFD2[VFD Primary Pump 2] --> CH2[Chiller 2]
VFD3[VFD Primary Pump 3] --> CH3[Chiller 3]
CH1 --> DIST[Distribution System]
CH2 --> DIST
CH3 --> DIST
DIST --> BPV[Bypass Valve]
BPV --> CH1
BPV --> CH2
BPV --> CH3
Minimum Flow Protection
Chillers require minimum flow to prevent evaporator freeze-up and ensure adequate heat transfer. Protection strategies include:
- Bypass valve: Opens when system flow drops below chiller minimum
- Pump minimum speed: VFD minimum frequency (typically 30-40 Hz)
- Chiller staging: Shut down chillers to maintain flow through operating units
Bypass valve sizing equation:
Where:
- $C_v$ = valve flow coefficient
- $\dot{V}_{gpm}$ = design flow rate through bypass
- $\Delta P_{psi}$ = differential pressure across valve (psi)
- $SG$ = specific gravity of fluid (1.0 for water)
Distributed Pumping
Distributed pumping places pumps at terminal units or zones rather than centrally. This approach optimizes pressure delivery, reduces pipe sizing, and enables independent zone operation but increases equipment count and maintenance complexity.
Applications include:
- High-rise buildings with significant elevation changes
- Campus systems with distributed buildings
- Retrofit installations adapting existing infrastructure
Pump head calculation for distributed systems:
Chiller Types and Performance
Chiller Classification
Chilled water systems employ various chiller technologies, each with distinct performance characteristics:
Chiller Performance Curves
Chiller efficiency varies with operating conditions, primarily affected by:
- Entering condenser water temperature (ECWT) or entering air temperature
- Leaving chilled water temperature (LCWT)
- Part-load ratio (PLR)
The integrated part-load value (IPLV) metric accounts for part-load operation:
Where A, B, C, D represent efficiency at 100%, 75%, 50%, and 25% load respectively.
Performance correction for non-standard conditions:
Typical centrifugal chiller part-load curve shows improving efficiency from 100% to 60-70% load:
Representative coefficients for variable-speed centrifugal:
- a = 0.15
- b = 0.20
- c = 0.30
- d = 0.35
Chiller Staging and Sequencing
Multiple chiller plants require optimization algorithms to minimize energy consumption. The fundamental approach stages chillers to maximize efficiency:
- Equal loading: Distribute load evenly across operating chillers
- Incremental efficiency: Stage next chiller when incremental efficiency improves
- Manufacturer curves: Use actual performance data for staging decisions
Staging decision criterion:
Where subscript $n$ represents current operating chillers and $n+1$ represents adding one additional chiller.
Pump Selection and Analysis
Pump Head Calculation
Total pump head consists of several components:
Friction Losses
Pipe friction follows the Darcy-Weisbach equation:
Where:
- $f$ = Darcy friction factor (dimensionless)
- $L$ = pipe length (ft or m)
- $D$ = pipe diameter (ft or m)
- $\rho$ = fluid density (lb/ft³ or kg/m³)
- $v$ = fluid velocity (ft/s or m/s)
Converting to head in feet of water:
For turbulent flow in commercial steel pipe, the Colebrook equation determines friction factor:
Where:
- $\epsilon$ = pipe roughness (ft), typically 0.00015 ft for steel
- $Re$ = Reynolds number = $\frac{\rho v D}{\mu}$
- $\mu$ = dynamic viscosity
Hazen-Williams equation provides simplified friction calculation:
Where:
- $H_f$ = friction head loss (ft per 100 ft)
- $\dot{V}$ = flow rate (gpm)
- $C$ = Hazen-Williams coefficient (120 for steel, 150 for copper)
- $D$ = inside diameter (inches)
Equipment Losses
Component pressure drops from manufacturer data:
Control Valve Authority
Control valve authority ensures adequate control range:
Target authority: 0.25-0.50 for acceptable control. Lower authority causes poor control and delta-T degradation.
Design valve pressure drop:
For $\beta$ = 0.33 and coil drop of 10 ft:
Pump Power and Efficiency
Pump power consumption derives from hydraulic principles:
Where:
- $P_{hydraulic}$ = hydraulic power (kW)
- $\rho$ = water density (kg/m³)
- $g$ = gravitational acceleration (9.81 m/s²)
- $\dot{V}$ = flow rate (m³/s)
- $H$ = total head (m)
In imperial units:
Actual motor power accounts for pump and motor efficiency:
Typical efficiencies:
- Pump: 70-85% (larger pumps more efficient)
- Motor: 90-95% (premium efficiency motors)
- VFD: 95-97%
Variable Speed Pumping
Variable frequency drives modulate pump speed to match system demand, following affinity laws:
Where:
- $\dot{V}$ = flow rate
- $H$ = pump head
- $P$ = power
- $N$ = rotational speed
- Subscripts 1 and 2 represent initial and final conditions
Energy savings from variable speed operation scale dramatically with the cubic relationship. Reducing speed to 75% (75% flow) reduces power to:
This relationship drives the economic justification for VFD implementation on chilled water pumps.
Differential Pressure Control
Control Strategies
Differential pressure (DP) sensors provide feedback for VFD pump speed control. Sensor location and setpoint strategy critically impact energy performance:
1. Fixed DP Setpoint at End of System
Traditional approach maintaining constant differential pressure at the critical (most remote) circuit:
Advantages:
- Guaranteed pressure at all loads
- Simple control logic
Disadvantages:
- Excessive pressure at partial load when remote loads are inactive
- Higher pumping energy
2. Reset DP Setpoint
Reduces differential pressure setpoint when control valves approach full open:
Where:
- $N_{open}$ = number of valves >90% open
- $N_{total}$ = total number of control valves
Typically implemented as:
- Reduce DP setpoint when all valves <90% open
- Increase DP setpoint when any valve >95% open
- Rate limit changes to prevent instability
Energy savings: 20-40% pump energy reduction compared to fixed DP.
3. Flow-Based Control
Directly controls pump to deliver required system flow based on load:
Requires flow meters on terminal circuits or calculated flow from control valve positions.
Sensor Placement
DP sensor location significantly affects control stability and energy performance:
- At pump discharge: Measures only pump-generated pressure, simple but provides no load feedback
- Two-thirds into distribution: Balances coverage of building zones
- Critical circuit: Ensures most remote load receives adequate pressure
- Multiple sensors: Use highest signal from multiple locations
Bypass Valves and Decoupling
Bypass Valve Functionality
Bypass valves (also called differential pressure bypass valves) protect chillers from low flow conditions in variable flow systems. The valve opens when system pressure exceeds setpoint, diverting flow from supply to return.
Bypass valve sizing methodology:
- Determine maximum bypass flow requirement:
- Calculate available differential pressure:
- Size valve coefficient:
Example: 1000 gpm chiller with 400 gpm minimum, 200 gpm minimum system flow, 60 psi pump pressure, 15 psi chiller drop:
Select next larger standard valve size.
Decoupler Design
In primary-secondary systems, the decoupler (common pipe) hydraulically separates primary and secondary loops. Proper design requires:
- Low pressure drop: <0.5 ft to prevent interaction
- Short length: 10-20 diameters to minimize mixing
- Bridge connections: Close spacing between supply and return connections
Decoupler pressure drop verification:
Temperature mixing when secondary exceeds primary flow:
Where:
- $\dot{V}{bypass} = \dot{V}{sec} - \dot{V}_{pri}$
- $T_{LCHWT}$ = leaving chilled water temperature from chillers
- $T_{RCHWT}$ = return chilled water temperature from building
Waterside Economizer Integration
Free Cooling Principles
Waterside economizers utilize low ambient conditions to provide cooling without chiller operation. When outdoor wet-bulb temperature drops sufficiently below required supply water temperature, a heat exchanger or direct cooling tower connection provides “free cooling.”
Available free cooling capacity:
Subject to constraint:
Where:
- $T_{WB,ambient}$ = ambient wet-bulb temperature
- $\Delta T_{approach}$ = cooling tower approach (typically 5-7°F)
- $\Delta T_{HX}$ = heat exchanger temperature difference (if used, 2-5°F)
Configuration Types
1. Plate-Frame Heat Exchanger
Indirect connection between condenser water and chilled water loops through heat exchanger:
graph LR
CT[Cooling Tower] --> CWP[Condenser Water Pump]
CWP --> HX[Plate-Frame HX]
HX --> CT
CHW[Chilled Water Return] --> HX
HX --> CHWSUP[Chilled Water Supply]
Heat exchanger effectiveness:
Typical effectiveness: 0.60-0.85 for counterflow plate-frame exchangers.
Required heat exchanger capacity:
Where log-mean temperature difference:
2. Integrated Waterside Economizer
Direct connection using cooling tower to chill building supply water through integrated chiller-economizer:
Advantages:
- No separate heat exchanger
- Lower first cost
- Reduced maintenance
Disadvantages:
- Water treatment criticality (tower water in building loop)
- Limited to integrated chiller designs
Control Sequences
Economizer operation modes:
- 100% free cooling: Chillers off, economizer provides full load
- Partial free cooling: Economizer pre-cools, chillers supplement
- Chiller-only: Ambient too warm for economizer benefit
Mode selection logic:
Energy savings calculation:
Where economizer energy includes:
- Condenser water pump
- Cooling tower fan
- Heat exchanger pump (if applicable)
Typical economizer energy: 0.05-0.15 kW/ton versus 0.50-0.70 kW/ton for chiller operation.
Thermal Storage Systems
Storage Fundamentals
Thermal energy storage (TES) shifts cooling production to off-peak periods, reducing demand charges and capitalizing on lower nighttime efficiency. The fundamental storage equation:
Where:
- $E_{stored}$ = stored energy (kWh or ton-hours)
- $m$ = mass of storage medium (kg or lb)
- $V$ = volume (m³ or gal)
- $\Delta T$ = temperature difference between charged and discharged states
Converting to ton-hours:
Storage Technologies
Storage Strategies
Full Storage
Chillers operate only during off-peak periods, storage meets entire on-peak load:
Where:
- $\dot{Q}_{peak}$ = peak cooling load
- $t_{discharge}$ = on-peak duration (hours)
Example: 500-ton peak load, 12-hour on-peak period, 16°F delta-T:
Partial Storage (Load Leveling)
Chillers operate continuously, storage supplements during peak periods:
Storage size based on area between load profile and chiller capacity:
Partial storage reduces chiller size and storage volume compared to full storage while still providing demand reduction.
Demand Limiting
Storage discharges only during utility demand peaks to minimize demand charges:
Storage System Hydraulics
Thermal storage requires careful piping design to maintain thermal stratification and prevent mixing.
Series configuration (charge-discharge flow path through storage):
graph LR
CH[Chiller] --> STG[Storage Tank]
STG --> LOAD[Building Load]
LOAD --> CH
Parallel configuration (storage in separate loop):
graph TD
CH[Chiller] --> DIV{Diverting Valve}
DIV --> LOAD[Building Load]
DIV --> STG[Storage Tank]
STG --> MIX{Mixing Valve}
LOAD --> MIX
MIX --> CH
Diffuser design for stratification:
Where:
- $Fr$ = Froude number (dimensionless)
- $v_{inlet}$ = inlet velocity (m/s)
- $g$ = gravitational acceleration (9.81 m/s²)
- $H$ = tank height (m)
- $\Delta \rho / \rho$ = relative density difference
Froude number <1 indicates stable stratification.
System Diversity and Load Profiles
Diversity Factors
Chilled water systems serving multiple zones rarely experience simultaneous peak loads. Diversity factors account for this non-coincident loading:
Typical diversity factors:
Applying diversity:
Where:
- $\text{DF}$ = diversity factor
- $\text{SF}$ = safety factor (1.10-1.20)
Load Duration Curves
Load duration curves plot cooling load against hours of occurrence, enabling energy analysis and equipment sizing optimization:
Key metrics from load duration analysis:
- Peak load: Maximum instantaneous demand
- Equivalent full-load hours: Total annual energy divided by peak load
- Part-load distribution: Percentage of hours at various load levels
Equivalent full-load hours:
Typical commercial buildings: 1,500-3,000 EFLH/year.
Bin Analysis
Bin analysis correlates building load with outdoor temperature for energy modeling:
Where:
- $T_{bin,i}$ = representative temperature for bin $i$
- $h_{bin,i}$ = hours in bin $i$
- $\dot{Q}(T)$ = building load at temperature $T$
- $\text{kW/ton}(T)$ = chiller efficiency at temperature $T$
Condenser Water Systems
Cooling Tower Fundamentals
Cooling towers reject heat from chiller condensers through evaporative cooling. The governing heat and mass transfer relationship:
Where:
- $\dot{m}_w$ = water mass flow rate
- $T_{CWR}$ = condenser water return temperature
- $T_{CWS}$ = condenser water supply temperature
- $\dot{m}_a$ = air mass flow rate
- $h$ = air enthalpy
Tower performance characterized by approach and range:
Where $T_{WB}$ = ambient wet-bulb temperature.
Typical design values:
- Approach: 5-7°F (tighter approach requires larger tower)
- Range: 10-15°F (matches chiller condenser delta-T)
Tower effectiveness:
Tower Selection and Sizing
Tower thermal capacity rated in terms of heat rejection:
For 500-ton chiller at 0.60 kW/ton (COP = 5.86):
Tower performance varies with operating conditions according to manufacturer curves, typically expressed as:
Variable Speed Tower Fans
Tower fan power follows cubic relationship with speed (affinity laws):
Fan speed modulates to maintain condenser water supply temperature setpoint. As ambient conditions cool, fan speed reduces, providing substantial energy savings.
Annual tower fan energy:
Where $P_{fan,h}$ varies with load and ambient conditions each hour.
Condenser Water Temperature Optimization
Lower condenser water temperature improves chiller efficiency but increases tower fan energy. The optimal setpoint balances these competing effects:
Minimize total power:
Typical optimal range: 65-75°F depending on load and ambient conditions.
Chiller power sensitivity to condenser water temperature:
For 500-ton chiller at 0.60 kW/ton base:
A 5°F reduction saves approximately 37.5 kW of chiller power.
Evaporative Loss and Makeup Water
Cooling towers lose water through evaporation, drift, and blowdown:
Evaporation rate:
Simplified:
Where $\dot{V}_{CW}$ = condenser water flow rate.
Blowdown maintains water quality by limiting concentration:
Where $\text{COC}$ = cycles of concentration (typically 3-6).
Total makeup water:
Drift typically 0.001-0.01% of circulation rate for modern drift eliminators.
Water Treatment and Corrosion Control
Water Quality Requirements
Chilled water and condenser water systems require chemical treatment to prevent:
- Corrosion of metallic components
- Scale formation from mineral precipitation
- Biological growth (algae, bacteria, fungi)
- Fouling from suspended solids
Critical water quality parameters:
Corrosion Mechanisms
Electrochemical corrosion occurs when dissimilar metals contact in an electrolyte (water):
Corrosion rate follows Faraday’s law:
Where:
- $I$ = corrosion current (A)
- $M$ = molecular weight (g/mol)
- $n$ = electrons transferred
- $F$ = Faraday constant (96,485 C/mol)
- $A$ = surface area (cm²)
- $\rho$ = density (g/cm³)
Typical corrosion rates expressed as mils per year (mpy):
- Excellent: <2 mpy
- Acceptable: 2-5 mpy
- Poor: >5 mpy
Scale Formation
Scale forms when mineral solubility limits are exceeded. Calcium carbonate represents the most common scale:
Langelier Saturation Index (LSI) predicts scaling tendency:
Where $\text{pH}_s$ = pH at calcium carbonate saturation.
Interpretation:
- LSI > 0: Supersaturated, scale-forming
- LSI = 0: Saturated, neutral
- LSI < 0: Undersaturated, corrosive
Target range: -0.5 to +0.5 for balanced condition.
Ryznar Stability Index provides alternate assessment:
Target RSI: 6.5-7.0 for stable conditions.
Treatment Strategies
Closed Loop Systems (Chilled Water)
Closed systems require one-time treatment with long-term inhibitors:
- Corrosion inhibitors: Sodium nitrite, sodium molybdate (200-1000 ppm)
- pH control: Sodium hydroxide or potassium hydroxide (pH 8.5-9.5)
- Biocides: Initial slug dose, periodic maintenance
Treatment concentration:
Inhibitor depletion rate typically 10-20% per year requires monitoring and makeup.
Open Loop Systems (Condenser Water)
Open systems continuously lose water through evaporation, requiring ongoing treatment:
- Scale inhibitors: Phosphonates, polymers (5-20 ppm)
- Corrosion inhibitors: Azoles, phosphates (2-10 ppm)
- Biocides: Oxidizing (chlorine, bromine) and non-oxidizing
- pH control: Acid feed for alkalinity management
Blowdown control maintains concentration:
Chemical feed rate:
Filtration
Side-stream filtration removes suspended solids:
Filter flow rate typically 1-10% of system flow:
Particle removal efficiency:
Energy Optimization Strategies
System-Level Optimization
Chilled water system energy consumption includes:
Optimization targets each component while maintaining comfort and reliability.
Chilled Water Temperature Reset
Raising chilled water supply temperature during low-load periods reduces chiller lift and improves efficiency:
Practical chiller efficiency improves approximately:
Reset schedule based on outdoor air temperature or load:
Typical range: 42°F at design load to 50-55°F at minimum load.
Constraints:
- Maintain adequate dehumidification (dewpoint control)
- Ensure terminal unit capacity at elevated temperature
- Monitor valve positions (reset limit when valves saturate)
Condenser Water Temperature Optimization
Discussed previously, balances chiller efficiency gains against tower fan energy:
Requires real-time optimization or pre-computed lookup tables.
Pump Speed Optimization
Variable speed pumps reduce energy consumption following cubic relationship:
Annual pump energy savings from variable speed:
Typical savings: 30-60% versus constant speed operation.
Control optimization:
- Differential pressure reset (described previously)
- Flow-based control matching demand
- Predictive control based on load forecasts
Chiller Plant Optimization
Multi-chiller plants require sequencing and load distribution optimization:
Objective function minimizes total plant power:
Subject to constraints:
- $\sum_{i=1}^{n} \dot{Q}i = \dot{Q}{load}$ (meet load requirement)
- $\dot{Q}_{min,i} \leq \dot{Q}i \leq \dot{Q}{max,i}$ (chiller capacity limits)
- $\dot{V}_{min,i} \leq \dot{V}_i$ (minimum chiller flow)
Solution methods:
- Lagrange multipliers: Analytical solution for differentiable curves
- Dynamic programming: Discrete optimization
- Real-time optimization: Use building automation system and chiller plant meter data
Equal marginal efficiency criterion:
Heat Recovery
Chiller condenser heat recovery captures rejected heat for simultaneous heating loads:
Available heat:
Condenser heat available at 85-105°F suitable for:
- Domestic hot water preheating
- Space heating during swing seasons
- Pool heating
- Process heating
Heat recovery effectiveness:
Economic analysis:
Where $\eta_{boiler}$ represents efficiency of displaced heating system.
Thermal Zoning and Diversity
Optimize chilled water distribution by thermal zones:
- Core zones: Constant cooling loads year-round
- Perimeter zones: Variable loads based on solar and envelope
- Process loads: Independent of weather
- Ventilation loads: Dependent on outdoor air conditions
Separate distribution enables:
- Temperature optimization by zone characteristics
- Reduced mixing losses
- Improved control and delta-T
Load aggregation diversity:
This vector sum acknowledges non-coincident peak conditions.
Practical Design Example
System Design Specification
Building: 200,000 ft² office building, 10 stories Location: Chicago, IL Cooling load: 800 tons peak (4.0 tons/1000 ft²) Hours of operation: 6 AM - 8 PM weekdays, 8 AM - 4 PM Saturday Design delta-T: 14°F (42°F supply, 56°F return)
Load Profile Analysis
Monthly peak loads:
Chiller Selection
Select three chillers for capacity, efficiency, and redundancy:
Configuration: Three 350-ton water-cooled centrifugal chillers with variable speed drives
Capacity analysis:
- Total installed: 1,050 tons (131% of peak)
- N+1 redundancy: 700 tons (87.5% of peak with one chiller down)
- Optimal loading: 267 tons per chiller at peak (76% of chiller capacity)
Performance specifications:
IPLV calculation:
Chilled Water Pumping
Configuration: Variable primary flow with three dedicated chiller pumps
Flow rate per chiller:
Head calculation:
- Pipe friction: 35 ft
- Chiller evaporator: 15 ft
- Coil pressure drop: 12 ft average
- Control valve: 5 ft
- Fittings and accessories: 8 ft
- Total: 75 ft
Pump power at design:
Select 20 hp motor with VFD.
Annual pumping energy (simplified):
Where $0.65^3$ represents average speed cubed based on load factor.
Condenser Water System
Cooling tower selection: Three 410-ton induced-draft counterflow towers with VFD fans
Heat rejection per tower:
(117% of chiller capacity based on 0.52 kW/ton)
Design conditions:
- Entering water: 95°F
- Leaving water: 85°F
- Range: 10°F
- Wet-bulb: 78°F
- Approach: 7°F
Condenser water flow:
Condenser water pump head:
- Pipe friction: 25 ft
- Chiller condenser: 20 ft
- Tower: 15 ft
- Control valve: 5 ft
- Fittings: 10 ft
- Total: 75 ft
Pump power per unit:
Select 30 hp motor with VFD.
Tower fan power: 15 hp per tower
Annual condenser water system energy:
Total System Energy
Annual energy summary:
System efficiency:
This represents excellent performance for a water-cooled centrifugal plant with optimized auxiliary equipment.
Economic Analysis
Capital cost estimate:
- Chillers (3 × $180,000): $540,000
- Cooling towers (3 × $45,000): $135,000
- CHW pumps (3 × $15,000): $45,000
- CW pumps (3 × $18,000): $54,000
- Piping and valves: $250,000
- Controls and instrumentation: $80,000
- Installation labor: $200,000
- Total: $1,304,000
Operating cost ($0.10/kWh):
Comparison to air-cooled system:
- Air-cooled efficiency: 1.05 kW/ton
- Air-cooled annual energy: 1,932,000 kWh
- Annual savings: 929,650 kWh × $0.10 = $92,965
- Simple payback: $304,000 incremental cost / $92,965 = 3.3 years
Conclusion
Chilled water system design requires integrated analysis of thermodynamic performance, fluid mechanics, heat transfer, and energy economics. Optimal configurations balance first cost, energy efficiency, reliability, and operational flexibility. Key design principles include:
- Delta-T preservation: Maintain design temperature difference through proper coil selection, balancing, and control valve authority
- Variable flow implementation: Utilize VFDs on pumps and tower fans to capture substantial energy savings at part-load conditions
- Chiller plant optimization: Select equipment sizes and implement controls to optimize total plant efficiency across the load spectrum
- Water quality management: Implement comprehensive treatment programs to prevent corrosion, scaling, and biological growth
- System diversity utilization: Account for non-coincident loads to rightsize equipment and reduce capital and operating costs
- Performance monitoring: Meter and track key parameters to verify design performance and identify optimization opportunities
The analytical methods presented enable rigorous system design based on fundamental physics and proven engineering principles. Proper application of these methodologies yields chilled water systems that deliver reliable, efficient cooling throughout their 20-30 year service life.