HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Natural Ventilation for Livestock Housing

Natural ventilation relies on naturally occurring pressure differences created by wind and thermal buoyancy to drive airflow through livestock buildings. This passive approach eliminates fan energy consumption and provides reliable ventilation without electrical power, making it ideal for moderate climates and facilities with adequate building height and proper orientation. The engineering challenge lies in sizing openings to provide sufficient airflow across widely varying outdoor conditions while maintaining acceptable air distribution patterns.

Stack Effect Fundamentals

Stack effect, also termed thermal buoyancy or chimney effect, develops when interior air temperature exceeds exterior temperature. The resulting density difference creates a pressure gradient that drives warm air upward and out through upper openings while drawing cool air in through lower openings.

The fundamental pressure difference from stack effect follows:

$$\Delta P_{stack} = h \cdot g \cdot (\rho_{out} - \rho_{in})$$

where $h$ represents the vertical distance between inlet and outlet centerlines (ft), $g$ equals gravitational acceleration (32.2 ft/s²), and $\rho$ denotes air density (lbm/ft³).

Expressing density in terms of temperature using the ideal gas law, the stack pressure becomes:

$$\Delta P_{stack} = h \cdot g \cdot \rho_{out} \cdot \left(1 - \frac{T_{out}}{T_{in}}\right)$$

where temperatures are absolute (°R = °F + 460).

Practical Example:

For a livestock barn with 16 ft height difference between sidewall inlets and ridge outlet:

  • Interior temperature: 70°F (530°R)
  • Exterior temperature: 30°F (490°R)
  • $\Delta P_{stack}$ = 16 × 32.2 × 0.0807 × (1 - 490/530) = 0.060 in. w.c.

This modest pressure drives natural ventilation airflow through properly sized openings.

Airflow Calculation Through Openings

Airflow through an opening follows the orifice equation:

$$Q = C_d \cdot A \cdot \sqrt{2 \cdot g \cdot h \cdot \left(1 - \frac{T_{out}}{T_{in}}\right)}$$

Converting to CFM for practical design:

$$Q_{CFM} = 9.4 \cdot A \cdot \sqrt{h \cdot \Delta T}$$

where $A$ is total opening area (ft²), $h$ is vertical separation (ft), and $\Delta T$ is temperature difference (°F).

Ridge Vent Sizing

Ridge vents provide continuous outlet opening along the building peak, maximizing stack height. Required ridge vent area per foot of building length:

$$A_{ridge} = \frac{Q_{total}}{9.4 \cdot L \cdot \sqrt{h \cdot \Delta T}}$$

Design Example:

200 ft long dairy barn requiring 60,000 CFM winter ventilation with $h$ = 14 ft and $\Delta T$ = 30°F:

$$A_{ridge} = \frac{60,000}{9.4 \times 200 \times \sqrt{14 \times 30}} = 1.56 \text{ ft}^2\text{/ft} = 225 \text{ in}^2\text{/ft}$$

Sidewall Opening Design

Sidewall openings serve as inlets for natural ventilation. For balanced flow:

$$A_{inlet} \approx 1.5 \times A_{outlet}$$

The larger inlet area compensates for lower pressure at inlet elevation and prevents excessive inlet velocities that create drafts. Design for maximum inlet velocity of 600-800 fpm.

Building WidthRidge Vent Area (in²/ft)Sidewall Area (in²/ft per side)
40 ft150225
60 ft180270
80 ft200300

Wind-Driven Ventilation

Wind creates surface pressure distributions that drive ventilation. Wind pressure follows:

$$\Delta P_{wind} = C_p \cdot \frac{\rho \cdot V^2}{2}$$

where $C_p$ is the pressure coefficient (+0.5 to +0.8 for windward walls, -0.3 to -0.5 for leeward walls) and $V$ is wind velocity (ft/min).

Wind-driven flow rate for cross-ventilation:

$$Q_{CFM} = 0.65 \cdot A \cdot V_{wind}$$

Example: 400 ft² opening with 10 mph wind (880 fpm) generates 228,800 CFM, demonstrating wind’s dominant effect during warm, breezy conditions.

Building Orientation

Optimize orientation for prevailing summer winds:

  • Long axis perpendicular to prevailing summer winds
  • Sidewall openings on both long sides
  • Ridge vent continuous along full length
  • End wall openings for variable wind directions

Curtain Management

Adjustable curtains control opening area across seasons:

Outdoor TemperatureCurtain PositionVentilation RateDriving Force
< 30°F3-6 inches open15 CFM/animal90% stack
30-50°F1-2 ft open30 CFM/animal70% stack
50-70°F3-4 ft open60 CFM/animal40% stack
> 70°FFully open (5-6 ft)100+ CFM/animal90% wind

Automated temperature sensors modulate curtain winches to maintain target temperature while preventing rapid cycling.

Design Limitations

Natural ventilation suits locations where:

  • Summer temperatures < 85°F majority of time
  • Winter temperatures > 10°F majority of time
  • Average wind speed > 5 mph
  • Temperature control band ±5°F acceptable

Supplemental mechanical fans assist during unfavorable conditions in hybrid systems.

Economic Analysis

Capital Cost:

  • Natural ventilation: $0.50-1.50 per ft² floor area
  • Mechanical ventilation: $1.50-3.00 per ft² floor area

Operating Cost:

  • Natural: $0 electrical consumption
  • Mechanical: $0.20-0.50 per ft² annually

Natural ventilation shows 50-70% lower installed cost and eliminates fan operating costs.


Natural ventilation harnesses stack effect and wind pressure to provide energy-free livestock housing ventilation through proper opening sizing, building orientation, and curtain management, suitable for moderate climates with adequate design considerations for airflow patterns and seasonal adjustment.